FW 08.01.00 McDATA® Sphereon 3032 and 3232 Fabric Switches Installation and Service Manual (620-000155-220, November 2005)

Table Of Contents
3
3-62
McDATA® Sphereon 3032 and 3232 Fabric Switches Installation and Service Manual
Diagnostics
Does the switch appear powered on?
YES NO
Analysis for an AC power distribution or CTP card failure is
not described in this MAP. Go to MAP 0000: Start MAP on
page 3-6. If this is the second time at this step, contact the
next level of support.
29
Either a switch-to-PC Internet link problem (Internet too busy or IP
address typed incorrectly) or a switch Ethernet port failure is
indicated.
a. Wait approximately five minutes, then attempt to login to the
switch again.
b. At the Netsite field (Netscape Navigator) or Address field
(Internet Explorer), type http://xxx.xxx.xxx.xxx, where
xxx.xxx.xxx.xxx is the IP address of the switch (obtained in
MAP 0000: Start MAP on page 3-6). The Username and
Password Required dialog box appears.
c. Type the user name and password (obtained in MAP 0000: Start
MAP on page 3-6) and click OK. If the View panel does not
display, wait another five minutes and perform this step again.
Does the EFCM Basic Edition interface appear operational with the
View panel displayed?
NO YES
The switch-to-EFCM Basic Edition PC connection is restored
and appears operational.
30
An unrecoverable Ethernet fault (reported as event code 433) is
indicated. The event code is not reported to the Sphereon 3032/3232
Event Log or the EFCM Basic Edition event log, and must be verified
through the switch maintenance port. A maintenance terminal
(desktop or notebook PC) and asynchronous RS-232 modem cable
are required to verify the reporting of event code 433. Both tools are
provided by installation or service personnel. To verify the event code:
a. Remove the protective cap from the 9-pin maintenance port at
the rear of the switch (a flat-tip screwdriver may be required).
Connect one end of the RS-232 modem cable to the port.