Diagnostics
10
Have the customer inspect and verify that facility power is within
specifications. These specifications are:
One single-phase connection for each power supply.
Input power between 120 and 230 Vac.
Input current between 2 and 4 amps.
Input frequency between 47 and 63 Hz.
Is facility power within specifications?
YES NO
Ask the customer to correct the facility power problem. When
facility power is corrected, verify switch temperature cools to
within the operational limit.
11
Inspect the fans. Do one or more fans appear to rotate at insufficient
angular velocity (failure pending)?
NO YES
Remove and replace the affected fan.(RRP: Cooling Fan FRU
on page 5-6). After fan replacement, verify switch
temperature cools to within the operational limit.
A power supply problem is indicated. Go to MAP 0100: Power
Distribution Analysis on page 3-27.
12
An SBAR module is not recognized by switch firmware because the
firmware version is not supported or the SBAR module failed. Advise
the customer of the problem and determine the correct firmware
version to download from the EFC Server.
Download the firmware (Download a Firmware Version to a Switch on
page 4-52). Perform the data collection procedure after the download.
Continue.
13
Did the firmware download solve the problem?
NO YES
The switch appears operational.