FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Edge Switch 2/32 Service Manual (AA-RS2GD-TE, July 2004)

Event Codes
279Edge Switch 2/24 Service Manual
Table 96: Event Code 604
Message: SBAR module failure.
Severity: Major.
Explanation: A failure criteria associated with the serial crossbar hardware module has been met.
Action: Perform the data collection procedure for the switch using HAFM, save the data file
to the HAFM appliance backup drive, and return the backup disk to HP support
personnel for analysis.
Event Data: Byte 0 = Slot position.
Byte 1 = Reason code:
00 = Operator requested with debug command.
02 = Initialization failure.
03 = Hot plug/power up diagnostics failure acknowledgement.
04 = Communications with hardware is irregular or nonexistent.
05 = Read of module ID failed.
06 = High availability statistical error threshold reached.
07 = Communication with hardware is irregular or nonexistent.
Bytes 4–7 = Elapsed millisecond tick counter.
Bytes 8–11 = Reason code specific data.
Distribution: Switch HAFM Appliance Host
EWS
Event Log
System
Error
Indicator
Event Log E-Mail Call
Home
Sense
Info
Link
Incident
✔✔✔✔✔✔
Table 97: Event Code 605
Message: SBAR module revision not supported.
Severity: Minor.
Explanation: The specified SBAR module is not recognized by the existing firmware. The SBAR
module will appear uninstalled to system software.
Action: Ensure that the switch model supports the operating firmware. If the firmware
supports the model, perform the data collection procedure for the switch using
HAFM. If the problem persists following a system power-on reset, replace the switch
and return the switch and the backup disk to HP support personnel for analysis and
repair.