FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Edge Switch 2/32 Service Manual (AA-RS2GD-TE, July 2004)

Diagnostics
35Edge Switch 2/24 Service Manual
Does the Status field display a Failed message for either power supply?
NO YES
A power supply failure is indicated. Go to step 18 to obtain event
codes. If no event codes are found, go to “MAP 0100: Power
Distribution Analysis” on page 51. Exit MAP.
17
Inspect the Status fields for switch FRUs.
Does the State field display a Failed message for any of the FRUs?
YES NO
The switch appears operational. Exit MAP.
A FRU failure is indicated. Continue to the next step to obtain event codes. If no
event codes are found, go to “MAP 0500: FRU Failure Analysis” on page 83. Exit
MAP.
18
Obtain event codes from the EWS Event Log.
Note: If multiple event codes are found, note all codes and associated severity levels.
Record the date, time, and listed sequence, and determine if the codes are related to
the reported problem. Begin fault isolation with the most recent event code with the
highest severity level. Other codes may accompany this event code, or may indicate a
normal indication after a problem is recovered.
1. At the View panel, click Monitor at the left side of the panel. The Monitor
panel opens with the Port List page displayed.
2. At the Monitor panel, click the Log tab. The Monitor panel (Log tab)
displays (Figure 7).