Diagnostics
59Edge Switch 2/24 Service Manual
MAP 0200: POST Failure Analysis
When the switch is powered on, it performs a series of power-on self-tests
(POSTs). When POSTs complete, the switch performs an initial program load
(IPL) that loads firmware and brings the unit online. This MAP describes fault
isolation for problems that may occur during the POST/IPL process.
If an error is detected, the POST/IPL process continues in an attempt to initialize
the switch and bring it online. But an event code 400 displays when the switch
completes the POST/IPL process.
1
Was an event code 400 or 411 observed at the switch Event Log (HAFM
appliance) or at the Embedded Web Server Event Log?
YES NO
Analysis for the failure is not described in this MAP. Go to “MAP 0000:
Start MAP” on page 29. Exit MAP.
2
The following table lists event codes, brief explanations of the codes, and the
associated steps that describe fault isolation procedures.
3
POST/IPL diagnostics detected a CTP failure as indicated by an event code 400
with supplementary bytes of event data.
Byte 0 is a FRU code (02) that indicates a failed CTP.
Byte 1 is the slot number (00) for the CTP.
Because the CTP card is not a FRU, CTP failure requires replacing the switch.
Table 6: MAP 200: Event Codes
Event
Code
Explanation Action
400 Power-up diagnostic failure. Go to step 3.
411 Firmware fault occurred. Go to step 4.