Replacing BA370, M2100 & M2200 Enclosure Elements
129HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software
Maintenance and Service Guide
3. For the operational controller, complete the following substeps:
a. Press Enter or Return within 3 minutes of completing substep 2f
above to exit FRUTIL, and then wait 1 minute to allow the
replacement controller to restart.
Note: If Enter or Return is not pressed within 3 minutes in substep 3a above, the
operational controller issues an automated command to cancel the installation of the
replacement controller. This cancellation causes all the port LEDs on the replacement
controller to go off. If this situation occurs, press Enter to exit
FRUTIL,
and then enter
the following command from the operational controller:
RESTART OTHER_CONTROLLER
b. Verify that the status of the cache of the operational controller is good
by entering the following command:
SHOW THIS_CONTROLLER
c. Complete one of the following steps from the operational controller:
If the controller reported that the cache and mirrored cache (if
enabled) is good in substep 3b, proceed to substep 3d below.
If the controller reported that the cache and mirrored cache (if
enabled) is not good in substep 3b, see Table 14 through Table 16
in theController and Cache Replacement Troubleshooting
appendix (which starts on page 253) to take corrective actions.
d. Disconnect the PC or terminal from the maintenance port of the
operational controller.