HP StorageWorks Multi-protocol Router Installation Guide (A7437-96003, September 2005)

Multi-protocol router installation guide 25
Installation guidelines
Install the MP Router using one of the following methods:
As a stand-alone unit on a flat surface
In a 19-inch Electronic Industries Association (EIA) rack, using the HP StorageWorks SAN Switch
Rack Mount Kit (included with the MP Router)
CAUTION: To ensure adequate cooling, install the chassis with the nonport side facing the
air-intake aisle. This prevents the fans from pulling in heated exhaust air.
Review these guidelines to ensure correct installation and operation:
Provide a space that is 2 rack units (2U) high (3.5 inches; 8.9 cm), 19 inches wide (48.3 cm),
and at least 28 inches deep (71.1 cm).
Position the MP Router with the nonport side facing the air-intake (cool) aisle.
Plan for cable management before installing the MP router. See ”Recommendations for cable
management” on page 40.
NOTE: IIf the cables will be routed below the chassis, leave a minimum of 3U of space below the
chassis.
Verify that two dedicated electrical branch circuits with the following characteristics are
available:
100 to 240 VAC, 47 to 63 Hz
Circuit breaker protection in accordance with local electrical codes
Supply circuit, line fusing, and wire size adequate to the electrical rating on the chassis
nameplate
Location close to the MP Router chassis, which is easily accessible
Grounded outlets installed by a licensed electrician, which are compatible with the power
cords
NOTE: To maximize fault tolerance, connect each power cord to a separate power source.
Verify that the MP Router fans have access to a total minimum air flow of 47 cubic feet per
minute (79.8 cubic meters per hour).
Verify that the air intake and exhaust vents have a minimum of 2 inches of airspace.
Ensure that the air temperature on the air intake side is less than 104
o
Fahrenheit (40
o
Celsius)
during operation.