HP StorageWorks SAN Switch 2/8V, 2/16V and 2/16N Installation Guide, V4.2.X (AA-RVULB-TE, April 2004)

Installing the SAN Switch
44 SAN Switch 2/8V, 2/16V and 2/16N Installation Guide
b. For the SAN Switch 2/8V, assemble the two inner rails (one on each side)
to the switch and plenum using the appropriate number (from step 5 on
page 42) of #8-32 x 5/16-inch Phillips pan-head SEMS screws as shown
in Figure 11.
Note: The plenum is a required part of this installation when the SAN switch 2/8V,
SAN switch 2/16V or 2/16N are installed in an HP 9000 or 10000 serires, System/e
or comparable EIA cabinet.
The plenum allows air to dissipate at the rear of the rack, preventing overheating. If the
Plenum is not pre-installed, refer to step b on page 44 for instructions.
Figure 11: Assembling the inner rails on a SAN Switch with plenum
The components in Figure 11 include:
7. Insert the switch with the attached inner rails into the outer rails.
1
Plenum
2
Switch
0013a
2
1