HP StorageWorks SAN Switch 2/8V, 2/16V and 2/16N Installation Guide, V4.2.X (AA-RVULB-TE, April 2004)

Technical Specifications
96 SAN Switch 2/8V, 2/16V and 2/16N Installation Guide
Environmental Requirements
To ensure proper operation, the switch must not be subjected to environmental
conditions beyond those for which it was tested. The ranges specified in Table 19
list the acceptable environment for both operating and non-operating conditions.
Note: The 0° - 40° Celsius range applies to the ambient air temperature at the air
intake vents on the nonport side of the switch. The temperature inside the switch can be
up to 75° Celsius during switch operation.
If the internal temperature range exceeds the operating ranges of the components, the
LEDs, error messages, and Fabric Watch alerts will indicate a problem. Enter the
tempshow or Fabric Watch commands to view temperature status.
Table 19: Environmental Requirements
Condition
Acceptable Range During
Operation
Acceptable Range During
Non-operation
Temperature -10° to +40° C (12° to 122° F) -50° to 100° C (-122° to
212
° F)
Humidity 20% to 85% RH non-condensing,
at 40
°C, with maximum gradient of
10% per hour
10% to 85% RH
noncondensing, at 70° C
Altitude 0 to 10,000 ft (3 km) above sea
level
0 to 39,370 ft (12 km) above
sea level
Shock 20 G, 6 ms duration, half sine wave 15 G, 12-18 ms duration,
trapezoid
Vibration 0.5 G, 5-500 Hz
2.0 G, 5-500 Hz
Air flow Normal: 24 cubic ft/minute
1 fan failed remaining running at
high speed): 30 cfm
All fans running at high speed: 44
cfm
None required