- HP X1000 G2 Netork Server Specification Sheet

Operating
LWAd
6.38 B
LpAm
52.77 dBA
X1500 G2
System Unit
Dimensions
(H x W x D)
(W/O footstand)
7.87 x 16.81 x 24.13 in (200 x 427 x 613 mm)
Weight
(approximate)
All hard drives, power
supplies, and processors
installed
30 kg
Input Requirements
(per power supply)
Rated Line Voltage
100 to 240 VAC
Rated Input Current
7.1 Amps (at 120VAC) to 3.5 Amps (at 240
VAC)
Rated Input Frequency
50 to 60 Hz
Rated Input Power
852 W
BTU Rating
Maximum
460W - 1773 BTU / hr (at 120 VAC), 1715
(at 240 VAC)
750W - 2892 BTU / hr (at 120 VAC), 2797
(at 240 VAC)
1200W - 3530 BTU / hr (at 120 VAC), 4600
(at 240 VAC)
System Inlet
Temperature
Operating
50° to 95° F (10° to 35° C) at sea level with an
altitude derating of 1.8°F per 1,000 ft (1.0° C per
every 305 m) above sea level to a maximum of
10,000 ft (3050 m) no direct sustained sunlight .
Maximum rate of change is 18°F/hr (10°C/hr). The
upper limit may be limited by the type and
number of options installed. System performance
may be reduced if operating with a fan fault or
above 86°F (30°C).
Non-operating
-22° to 140° F (-30° to 60° C)
Relative Humidity
(non-condensing)
Operating
10% to 90% relative humidity (Rh), 82.4°F
(28°C) maximum wet bulb temperature,
noncondensing.
Non-operating
10% to 95% relative humidity (Rh), 101.7°F
(38.7°C) maximum wet bulb temperature,
noncondensing.
Altitude
Operating
10,000 ft (3000m). Maximum allowable altitude
change rate is 1°C per 300m.
Non-operating
10,000 ft (3000m). Maximum allowable altitude
change rate is 1°C per 300m.
Acoustic Noise
Listed are the declared A-Weighted sound power levels (LWAd) and declared
average bystander position A-Weighted sound pressure levels (LpAm) when
the product is operating in a 23°C ambient environment. Noise emissions were
measured in accordance with ISO 7779 (ECMA 74) and declared in accordance
with ISO 9296 (ECMA 109).
QuickSpecs
HP X1000 G2 Network Storage Systems
Technical Specifications
DA - 13839 North America — Version 11 — December 28, 2012
Page 46