Brocade Fabric OS Message Reference Guide (53-1000242-01, November 2006)

Fabric OS Message Reference 18-7
Publication Number: 53-1000242-01
FCR-1021
18
Recommended
Action
Remove excess LSAN zones so that the number of LSAN zones created is within the range of the local
database limitations.
Severity WAR NIN G
FCR-1021
Message
Probable
Cause
Indicates that the number of devices created through LSAN zones within the MetaSAN is greater than
the local LSAN zone database limitations.
Recommended
Action
Remove excess device entries within LSAN zones so that the number of devices is within the range of
the local zone database limitations.
Severity WAR NIN G
FCR-1022
Message
Probable
Cause
Indicates that the resources used to persistently store the proxy device slot to the remote WWN have
been consumed.
Recommended
Action
You might need to remove the proxy device slots by using the fcrProxyConfig command or limit proxy
devices by removing LSAN zone entries.
Severity ERROR
FCR-1023
Message
Probable
Cause
Indicates that the number of port WWNs in use is greater than the local port WWN resources.
<timestamp>, [FCR-1021], <sequence-number>,, WARNING, <system-
name>, Local LSAN device entries exhausted.
<timestamp>, [FCR-1022], <sequence-number>,, ERROR, <system-name>,
Local proxy device slot entries exhausted.
<timestamp>, [FCR-1023], <sequence-number>,, WARNING, <system-
name>, Local phantom port WWN entries exhausted.