Brocade Fabric OS Message Reference - Supporting Fabric OS v7.0.1 (53-1002448-01, March 2012)

Fabric OS Message Reference 189
53-1002448-01
EM-1035
25
EM-1035
Message <timestamp>, [EM-1035], <sequence-number>,, ERROR, <system-name>, 2 circuit
paired Power Supplies are faulty, please check the <Switch side> AC main
switch/circuit to see if it has power.
Probable Cause Indicates that both power supplies associated with one of the two main circuits are present but
faulty, may be the circuit's switch has been turned off, or the AC power source has been interrupted
for that circuit.
The Switch side value designates the circuit switch, facing the cable side of the chassis, and is one
of the following:
left - Controls the odd numbered power supply units.
right - Controls the even numbered power supply units.
Recommended
Action
Verify that the identified AC circuit switch is turned on, the power cord is properly attached and
undamaged, and the power source is operating properly.
Severity ERROR
EM-1036
Message <timestamp>, [EM-1036], <sequence-number>,, WARNING, <system-name>, <FRU Id> is
not accessible.
Probable Cause Indicates that the specified field-replaceable unit (FRU) is not present on the switch.
If the FRU is a World Wide Name (WWN) card, the default WWN and IP addresses are used for the
switch.
Recommended
Action
Reseat the FRU.
If the problem persists, restart or power cycle the switch.
Execute the diagPost command to make sure that Power-On Self-Test (POST) is enabled; then
power cycle the blade using the slotPowerOff and slotPowerOn commands or have the blade's
ejector switch cycled to run POST and verify that the blade does not have any hardware problems.
If the problem still persists, replace the FRU.
Severity WARNING
EM-1037
Message <timestamp>, [EM-1037], <sequence-number>,, INFO, <system-name>, <FRU Id> is no
longer faulted.
Probable Cause Indicates that the specified power supply is no longer marked faulty; probably because its AC power
supply has been turned on.