Brocade Fabric OS Message Reference - Supporting Fabric OS v7.0.1 (53-1002448-01, March 2012)

432 Fabric OS Message Reference
53-1002448-01
HIL-1202
48
If the fan continues to generate this message, replace the fan FRU.
Severity WARNING
HIL-1202
Message <timestamp>, [HIL-1202], <sequence-number>,, ERROR, <system-name>, Blower <blower
number> faulted, speed (<measured speed> RPM) below threshold.
Probable Cause Indicates that the specified fan speed (in RPMs) has fallen below the minimum threshold.
Recommended
Action
Replace the fan FRU.
Severity ERROR
HIL-1203
Message <timestamp>, [HIL-1203], <sequence-number>,, ERROR, <system-name>, Fan <fan
number> faulted, speed (<measured speed> RPM) above threshold.
Probable Cause Indicates that the specified fan speed (in RPMs) has risen above the maximum threshold. A high
speed does not necessarily mean that the fan is faulty.
Recommended
Action
Run the tempShow command to verify that the switch temperatures are within operational ranges.
Refer to the hardware reference manual for the temperature range of your switch.
Make sure that the area is well-ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
Run the fanShow command to monitor the speed of the fan generating this error.
If the fan continues to generate this message, replace the fan FRU.
Severity ERROR
HIL-1204
Message <timestamp>, [HIL-1204], <sequence-number>,, ERROR, <system-name>, Fan <fan
number> faulted, speed (<measured speed> RPM) below threshold.
Probable Cause Indicates that the specified fan speed (in RPMs) has fallen below the minimum threshold. This
message is specific to nonbladed switches and is not applicable to the Brocade 24000 or 48000.
Recommended
Action
For the Brocade 3900 replace the fan FRU.
For the Brocade 3016, 3250 and 3850, the entire switch must be replaced because these
switches do not have field-replaceable units (FRUs).
Severity ERROR