Adding and Configuring Components

Step 10.
Using a Volt-Ohm meter (VOM), check the following test points to make sure they conform
to the specifications for the PDCA and local electrical specifications:
Table 1 Four- and Five-Wire Voltage
Ranges
Four-Wire Five-Wire
L2 to L3: 200-240 V
L1 to N: 200-240 V
L2 to L1: 200-240 V L2 to N: 200-240 V
L1 to L3: 200-240 V
L3 to N: 200-240 V
N to Ground:
1
Figure 3 Checking PDCA Test Points (five-Wire)
Adding additional PDCAs