Site Preparation Guide, Eighth Edition - Superdome HP 9000 Systems

Chapter 1
System Specifications
Electrical Specifications
14
Example 1-1 The customer has a 3-phase source with a Source Voltage of 208 VAC measured
phase-to-phase indicating that a 4-wire PDCA is required.
Example 1-2 The customer has a 3-phase source with a Source Voltage of 220 VAC measured
phase-to-neutral indicating that a 5-wire PDCA is required.
Example 1-3 The customer has a 3-phase source with a Source Voltage of 230 VAC measured
phase-to-phase indicating that a 4-wire PDCA is required.
Example 1-4 The customer has a 3-phase source with a source voltage of 415 VAC measure
phase-to-phase and a measured phase-to-neutral source voltage of 240 VAC,
indicating a 5-wire PDCA is required.
Input Power Options
Table 1-6 describes the available power options:
Table 1-6 Available Power Options
PDCA
Product
Number
Source
Type
Source Voltage
(nominal)
PDCA
Required
Input Current
Per Phase
200-240 VAC
In-line Connector
Required
A5800A
Option 001
a
3-phase Voltage range
200-240 VAC,
phase-to-neutral,
50/60 Hz
(EUR typical)
b
5-wire 24A Maximum
per phase
None required.
Electrician must hard
wire power to the
PDCA
c
A5800A
Option 002
a
3-phase Voltage range
200-240 VAC,
phase-to-phase,
50/60 Hz
(US typical)
4-wire 44A Maximum
per phase
None required.
Electrician must
hard-wire power to the
PDCA
c
A5800A
Option 004
d
3-phase Voltage range
200-240 VAC,
phase-to-phase,
50/60 Hz
(US typical)
4-wire 44A Maximum
per phase
In-line connector and
plug provided with a
2.5-meter power cable.
Electrician must
hard-wire in-line
connector to 100A site
power.
c,e