Site Preparation Guide, Eighth Edition - Superdome HP 9000 Systems

Chapter 1
System Specifications
Electrical Specifications
15
A5800A
Option 005
d
3-phase Voltage range
200-240 VAC,
phase-to-neutral,
50/60 Hz
(EUR typical)
5-wire 24A Maximum
per phase
In-line connector and
plug provided with a
2.5-meter power cable.
Electrician must
hard-wire in-line
connector to 60/63A
site power.
c,e,f
A5800A
Option 006
g
3-phase Voltage range
200-240 VAC,
phase-to-phase,
50/60 Hz
4-wire 44A Maximum
per phase
2.5meter UL power
cord and UL approved
plug provided. The
customer must provide
the mating in-line
connector or purchase
quantity one A6440A
opt 401 to receive a
mating inline
connector. An
electrician must hard
wire the in-line
connector to 60A/63A
site power.
c,f,h
A5800A
Option 007
i
3-phase Voltage range
200-240 VAC,
phase-to-neutral,
50/60 Hz
5-wire 24A Maximum
per phase
2.5meter <HAR>
power cord and VDE
approved plug
provided. The
customer must provide
the mating in-line
connector or purchase
Quantity 1 A6440A opt
501 to receive a mating
in line connector. An
electrician must hard
wire the in-line
connector to 30A/32A
site power.
c,h,j
a. Options 1 and 2 have been deleted.
b. 415 VAC phase-to-phase is possible.
c. A dedicated branch is required for each PDCA installed.
d. Options 4 and 5 have been deleted.
e. Refer to Table 1-7 for detailed specifics related to this option.
f. In the U.S.A., site power is 60 Amps; In Europe site power is 63 Amps.
g. Customer must provide in-line connector or purchase A6440A option 401.
h. Refer to Table 1-8 for detailed specifics related to this option.
i. Customer must provide in-line connector or purchase A6440A option 501.
Table 1-6 Available Power Options (Continued)
PDCA
Product
Number
Source
Type
Source Voltage
(nominal)
PDCA
Required
Input Current
Per Phase
200-240 VAC
In-line Connector
Required