Site Preparation Guide, Eighth Edition - Superdome HP 9000 Systems

Chapter 1
System Specifications
Electrical Specifications
29
I/O Expansion Cabinet Power Requirements
The I/O expansion cabinet requires a single phase 200-240VAC input. Table 1-11 lists the AC power
requirements for the I/O expansion cabinet.
NOTE The IOX accommodates two AC inputs for redundancy
I/O Expansion Cabinet Power Cords
Table 1-13 lists the power cords for the I/O expansion cabinet.
Peripheral Cabinet Power Requirements
There is a high probability that an existing peripheral cabinet may be incorporated into this system. Ensure
that adequate power is available for this cabinet and the associated peripherals.
Table 1-11 I/O Expansion Cabinet Power Requirements (without Support
Management Station)
Requirements Value
Nominal input voltage 200-240 VAC
Input voltage range (minimum-maximum) 200-240 VAC
Frequency range (minimum-maximum) 50/60 Hz
Number of phases 1
Marked Electrical input current 16A max
Maximum inrush current 60 A peak
Power factor correction 0.95 minimum
Table 1-12 I/O Expansion Cabinet Component Power Requirements
Power Required (50 - 60 Hz) VA
Fully configured cabinet 3200
I/O cardcage 500
ICE 600
Table 1-13 I/O Expansion Cabinet AC Power Cords
Part Number
A5499AZ
Where Used Connector Type
-001 North America L6-20