Site Preparation Guide, Eighth Edition - Superdome HP 9000 Systems

Chapter 2
Electrical and Environmental Guidelines
Electrical Factors
40
The minimum recommended illumination level is 70 foot-candles (756 lumens per square meter) when the
light level is measured at 30 inches (76.2 cm) above the floor.
Power Quality
This equipment is designed to operate over a wide range of voltages and frequencies. It has been tested and
shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are exceeded.
Severe electrical disturbances can exceed the design specifications of the equipment.
Sources of Electrical Disturbances
Electrical disturbances, glitches, affect the quality of electrical power. Common sources of these disturbances
are:
Fluctuations occurring within the facility’s distribution system
Utility service low-voltage conditions (such as sags or brownouts)
Wide and rapid variations in input voltage levels
Wide and rapid variations in input power frequency
Electrical storms
Large inductive sources (such as motors and welders)
Faults in the distribution system wiring (such as loose connections)
Microwave, radar, radio, or cell phone transmissions
Power System Protection
Computer systems can be protected from the sources of many of these electrical disturbances by using:
A Protective Earth (PE) connection with a wire diameter of at least equal to the current carrying
conductors. The neutral conductor must not be used for the PE connection. (The PE wire is GREEN with
a YELLOW stripe.)
A dedicated power distribution system
Power conditioning equipment
Over- and under-voltage detection and protection circuits
Screening to cancel out the effects of undesirable transmissions
Lightning arresters on power cables to protect equipment against electrical storms
Every precaution has been taken during power distribution system design to provide immunity to power
outages of less than one cycle. However, testing cannot conclusively rule out loss of service. Therefore,
adherence to the following guidelines provides the best possible performance of power distribution systems
for Superdome server equipment:
Dedicated power source—Isolates server power distribution system from other circuits in the facility.
Missing-phase and low-voltage detectors—Shuts equipment down automatically when a severe power
disruption occurs. For peripheral equipment, these devices are recommended but optional.
Online uninterruptable power supply (UPS)—Keeps input voltage to devices constant and should be
considered if outages of one-half cycle or more are common. Refer to qualified contractors or consultants
for each situation.