Superdome Servers - I/O Expansion Cabinet Guide, Fifth Edition
Chapter 5
Adding an ICE to the IOX
Connecting the Cables
120
Step 2. Pass the cable from the back of the XPC, down the nearest rack channel, over the cable
management arm, under the strain relief arm of the newly installed ICE. Be sure to add enough
service loop when routing the cable to allow the ICE to extend fully.
Figure 5-28Routing ICE DC Power Cable
Step 3. Locate the power connector on the back of the ICE. See Figure 5-11 on page 105.
Step 4. Secure the connector. Secure the cable to the strain relief arm, the roller management arm, and the
rear of the ICE chassis at the Tee-bar or cable bundle bracket.
4/13/01
60IOX060
See Detail A
See Detail B
Detail A
Detail B
DC Power Input
J2
I/O BAY 2
From J4 on XPC
J1
I/O BAY 1
J0
I/O BAY 0