System Specifications
Electrical Specifications
197
Electrical Specifications
This section provides electrical specifications for the IOX cabinet.
AC Power Requirements
The operating input voltage range is 176-264 VAC rms at line frequencies of 47-63 Hz. The XPC accepts one
or two single phase inputs. The nominal input voltage range is 200-240 VAC rms.
Table A-5 lists the AC power requirements for a IOX cabinet. This table provides information to help you
determine the amount of AC power needed for your computer room.
For redundant AC operation (n+1=2) utilizing two input power grids, one single phase is received from power
grid no. 0 and one single phase from power grid no. 1. Note the input power grids are not required to be equal
in voltage or equal in phase angle.
Table A-5 AC Input and Output Requirements
Requirement Value or Range Conditions or Comments
Nominal Input Voltage (VAC rms) 200 to 240
Input Voltage Range (VAC rms) 176-264
Frequency Range (Hz) 47-63
Maximum Inrush AC Current (A
Peak)
30A Maximum Total for two slots populated.
Maximum Input Current Per BPS (A
rms)
20A @200 vac24A @176 vac
Number of Phases 1 One phase per power AC input.
Ground Leakage Current less than 3.5 mA