HP StorageWorks 200 Storage Virtualization System site preparation guide (AE071-96003, October 2006)

Weight and ot
her parameters
The followin
g tables list components of the HP SVS200 and provide approximate values (rounded up) for
weight, heat
output, power requirements, and air ow requirements. We recommend you use the totals
shown for a f
ully optioned system so you will not have to modify your site if you add o ptions later. The
second table shows the maximums if you add a second HP SVS200 Controller with all options in the
same rack. Packaging for delivery adds approximately 23 kg/50 lbs to the total weights shown.
Component specications and totals for one SVS200 Controller
Component
kg/lbs
Heat
kW
Power
kVA
Air
ow
cubic
M/s
HP SVS200 Rack Assembly (maximum)
180/396
000
HP SV S2 00
Controller 1–127+ TB Bundle
(maximum
)
101/222
1.2 1.2 7.0
Options (maximum values if all available
options are added)
24/54
0.7 0.7 0
TOTALS, ONE HP SVS200 Controller with all
available options
305/672
1.9 1.9 7.0
Compon
ent specications and totals for two SVS200 Controllers
Component
kg/lbs
Heat
kW
Power
kVA
Air
ow
cubic
M/s
HP SVS200 Rack Assembly (maximum)
180/396
000
HP SVS200 Controller 1–127+ TB Bundle
(maximum)
101/22
2
1.2 1.2 7.0
Options (maximum values if all available
options are added)
24/54
0.7 0.7 0
Second HP SVS200 Controller 1–127+ TB
Bundle (maximum)
101/222
1.2 1.2 7.0
Seco
nd Set of Options (maximum values if
all a
vailable options are added)
24/5
4
0.7 0.7 0
TOTALS, TWO HP SVS200 Controllers in one
rack with all available options
430/948
3.8 3.8 14.0
18 Site requirements