General computer room requirements
The goal of a computer room is to ma intain an ideal environment for computer equipment, including
this system.
Make sure you
r computer room adheres to all national and local building codes for a data
center/com
puter room environment.
HP recommends that you follow these general guidelines:
Locate the computer room away from exterior walls of the building to avoid the heat gain from
windows and exterior wall surfaces.
When exter
ior windows are unavoidable, use windows that are double or tripled glazed and
shaded to p
revent direct sunlight from entering the computer room.
Maintain the computer room at a positive pressure relative to the surrounding spaces to reduce
introduction of contaminants.
Install a vapor barrier around the entire computer room envelope (oors/walls/ceiling) to help
keep moisture out of the room. This is especially important if your comp uter room is located
undergr
ound.
Caulk and vapor-seal all pipes a nd cables that penetrate the computer room envelope.
Preventing electrostatic discharge
Electrostatic d ischarge (ESD) can cause component damage, especially during servicing operations.
Static charges occur when objects are separated or rubbed together. The voltage level of a static charge
is determined by the following factors:
Types of materials
Relative humidity low humidity tends to increase ESD voltage.
Rate of change a standard air conditioner cools the air and lowers humidity. The faster the air
is cooled and dried, the greater the likelihood of ESD.
Separation refers to the static discharge that can be generated when two objects are
separated. For example, printer paper is often stored in cool dry conditions. If op ened and used
immediately, the act of removing the paper from its box generates static.
Follow these precautions to minimize possible ESD-induced failures in your computer room:
Install conductive ooring (conductive adhesive must be used when laying tiles).
Useconductivewaxifwaxedoors are installed.
Ensure that all equipment and ooring are properly grounded and are at the same ground
potential.
Use cond uctive tables and chairs.
Store spare electric parts in antistatic containers.
Use proper cooling equipment to reduce the risk of ESD by maintaining recommended humidity
level and airow rates.
Leave boxes of paper open in the computer room for several hours before use to allow static
to discharge gradually over time.