HP StorageWorks 200 Storage Virtualization System site preparation guide (AE071-96003, October 2006)

Environmental requirements
The environmental specications for op erating this system must b e satised before installation.
Altitude
The maximum altitude for system operation is 3,000 meters. For nonoperational or stora g e situations,
the maximum altitude is 4,000 meters.
Air conditi
oning
Use separa
te computer room air conditioning duct work. If it is not separate from the rest of the building,
it might be
difcult to control cooling and a ir pressure levels. Duct work seals are important for
maintaining a balanced air conditioning system and high static air pressure. Adequate cooling capacity
means little if humidity levels increase when the ducts are exposed to warm air, producing condensation.
Condensation on any disk hardware can damage the components.
Any questions regarding the adequacy of airow construction should be referred to and evaluated by a
qualied structural engineer.
Temperature specications
Temperature range type Range
Recommended operating temperature range 21 to 24 degrees C
70 to 75 degrees F
Operating temperature
16 to 32 degrees C
61 to 89 degrees F
Nonoperating temperature range
–10 to +
43 degrees C
14 to 10
9 degrees F
Shipping and storage temperature (product packed
in factory packing)
–25 to +60 degrees C
13to+140degreesF
Temperature shock immunity (maximum rate of
temperature change)
10 degrees C per hour
18 degrees F per hour
28 Site requirements