HP StorageWorks 200 Storage Virtualization System site preparation guide (AE071-96003, October 2006)

European AC power cabling
The HP SVS200 rack requires 20-a mp, single-phase 200 VAC power supplied by four power cords with
plugs, four receptacles, and four main disconnect devices (circuit breakers).
The HP SVS200 comes from the HP factory with the AC power cables and plugs or stripped ends you
have ordered. Plug types are specied under the heading, AC inputs. The opposite end of the power cord
connects to the HP SVS200 power distribution unit (PDU) input, which is a t ype IEC 320-C20 connector.
European branch circuit requirements
To protect the system, your bu ilding must be wire d correctly. Each supply (“hot”) c onductor must be
protectedbyashort-circuitprotectivedeviceandbyanovercurrentprotectivedevice. Thetablelisted
under AC inputs provides specications for the overcurrent protective devices required for single-phase
operation. All protective devices must comply with national standards of the countr y where the unit is
to be installed. If a protective device interrupts any supply conductor, it must also interrupt all other
supply conductors.
Overcurrent protection is also required for the neutral conductor.
Your electrician should know the appropriate code requirements for your location/site and wire power
distribution to the HP SVS200 accordingly.
HP StorageWorks 200 Storage Virtualization System site preparation guide