HP StorageWorks 200 Storage Virtualization System site preparation guide (AE071-96003, October 2006)

Connecting t
he European power-supply cables
Connect ea ch AC power cable to a separate receptacle on a separate circuit breaker, and connect each
pair of power cords (the left pair and the right pair) to separate distribution panels to ensure power fault
tolerance. Single-phase power cable wiring is shown in the gure below.
CAUTION:
Do not apply
power until instructed to do so by HP. An HP representative should be present whenever the
system is being connected to a new power source.
CAUTION:
Besuretoconnectthepowercordstothedistributionpanelasshowninthegure. Improper wiring of
theneutralconductormaycausedamagetotheHPsystem.Toreducetheriskofawrongconnection,
useaplugandsocketthatareapprovedforthissystem.Itisyourelectriciansresponsibilitytoselectand
install the proper plugs and receptacles.
WARNING!
High leakage current can occur between the power supply and the unit. To avoid electrical shock, be
sure to make the protective earth connection before the supply connections.
42
Electrical specications