HP R3000v UPS User Manual
INSTALLATION
HP R3000v UPS User Guide S 164201731 Rev 1
9
CAUTION
The ERM is heavy (see page 35). A minimum of two people are required to lift the cabinet into
the rack.
11. Slide the UPS and any optional cabinets into the rack.
12. Secure the front of the UPS to the rack using two M6
×16 pan-head screws and two
M6 cage nuts on each side (see Figure 6). Install the bottom screw on each side
through the bottom hole of the mounting bracket and the bottom hole of the rail
assembly.
Repeat for any optional cabinets.
M6×16 Pan-Head
Screws (4 places)
M6 Cage Nuts
(4 places)
Figure 6 Securing the Front of the Cabinet
13. Optional. Insert a rear stop bracket through the inside of each rail assembly behind the
UPS. Rotate each bracket and slide the bracket until it fits tightly against the UPS’s rear
panel. Secure each bracket to the UPS with one M3
×8 pan-head screw. See
Figure 7.
Repeat for any optional cabinets.
Rear Stop Bracket
M3
×8 Pan-Head Screw
Figure 7 Securing the Back of the Cabinet (Optional)
14. Continue to “Rackmount Wiring Installation” on page 10.