HP R3000v UPS User Manual
UPS MAINTENANCE
HP R3000v UPS User Guide S 164201731 Rev 1
28
Replacing UPS Internal Batteries
CAUTION
The UPS internal batteries are heavy. Use caution when handling the heavy batteries.
The internal batteries are located behind the UPS right front bezel. The internal batteries are
packaged together as one unit for easier handling.
To replace the UPS internal batteries:
1. RemovetheUPSrightfrontbezel(seeFigure20).
To remove the bezel, loosen the two captive screws on the right side of the bezel.
Grasp the top and bottom of the bezel and slide the bezel to the right.
NOTE: A r ibbon cable connects the control panel to the UPS. Do not pull on the cable or
disconnect it.
NOTE: Leave
ribbon cable
connected.
Figure 20 Removing the UPS Right Front Bezel
2. Disconnect the internal battery connector (see Figure 21).
Internal Battery
Connector
Battery Cover Plate
Figure 21 Disconnecting the UPS Internal Batteries (Shown without ERMs)