HP R3000v UPS User Manual
HP R3000v UPS User Guide S 164201731 Rev 1
35
Chapter 7 Specifications
This section provides the following specifications:
S Weights and dimensions
S Model specifications
S Electrical input and output
S Environmental and safety
S Battery
Table 4 Weights and Dimensions
Model
Dimensions (H×W×D)
Weight
HP R3000v UPS
86.7×438.0×602.4 mm
(3.41”
×17.24”×23.72”)
31.4 kg (69.2 lb)
HP R3000v ERM
86.7×438.0×601.6 mm
(3.41”
×17.24”×23.69”)
38.1 kg (84.0 lb)
Table 5 Model Specifications
Model HP R3000v UPS
Power Level 3000 VA, 2100W
Communication Ports RS-232 (DB-9): 2400/4800/9600 bps
USB: 2400 bps
Table 6 Electrical Input
Nominal Frequency 50/60 Hz auto-sensing
Frequency Range 40–70 Hz before transfer to battery
Bypass Voltage Range +10/-15% of nominal (default)
Noise Filtering MOVs for normal a nd common mode noise
Default Input (Voltage/Current) 230V/13.0A
Selectable Input Voltages 200*, 208**, 220, 230, 240
Voltage Range at 100% Load 180–276 Vac
Input Connection IEC C20-16A
Input Cable Schuko 16A to IEC 320-16A
* 100V and 200V are derated by 20%.
** 110V and 208V are derated by 10%.