HP R3000v UPS User Manual
SPECIFICATIONS
HP R3000v UPS User Guide S 164201731 Rev 1
36
Table 7 Electrical Output
Output Connections (8) IEC 320-10A, (1) IEC 320-16A
Nominal Outputs 200/208/220/230/240V
(voltage configurable or auto-sensing)
3kVA,2.1kW
Voltage Regulation (Normal mode) ±2%
Voltage Regulation (Battery mode) Nominal output voltage ±3%
Efficiency (Normal mode) >88%
Efficiency (Battery mode) >84%
Frequency 50 or 60 Hz, auto-sensing or configurable as a frequency converter
Frequency Regulation (Normal mode) Sync with line ±3 Hz of nominal line frequency
(outside this range: ±0.1 Hz of auto-selected nominal frequency)
Frequency Regulation (Battery mode) ±0.1 Hz of auto-selected nominal frequency
Output Overload (Normal mode) 100–102%: Activates Overload alarm. (Level 1)
102–129%: Load transfers to Bypass mode after 12 seconds. (Level 2)
130–149%: Load transfers to Bypass mode after 2 seconds. (Level 3)
>
150%: Load transfers to Bypass mode after 100 ms. (Level 4)
NOTE: Default configuration transfers immediately to bypass at >102%.
Output Overload (Bypass mode) 100–109%: Activates Overload alarm. (Level 1)
110–129%: UPS shuts down after 5 minutes. (Level 2)
130–149%: UPS shuts down after 15 seconds. (Level 3)
>
150%: UPS shuts down after 300 ms. (Level 4)
Output Overload (Battery mode) 100–102%: Activates Overload alarm. (Level 1)
102–129%: UPS shuts down after 12 seconds. (Level 2)
130–149%: UPS shuts down after 2 seconds. (Level 3)
>
150%: UPS shuts down after 100 ms. (Level 4)
Voltage Waveform Sine wave
Harmonic Distortion <3%THDonlinearload;<5%THDonnon-linearload
Transfer Time Online mode: 0 ms (no b reak)
Power Factor 0.7
Load Crest Factor 3to1