Table 8 Environmental and Safety
Surge Suppression IEC/EN 61004-5
EMC Certifications IEC/EN 62040-2, Emissions: Category C2, Immunity: Category C2
EMC (Emissions) IEC 62040-2:ed2:2005; EN 62040-2:2006
Safety Conformance IEC 62040-1-1
Operating Temperature 0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude
NOTE: Thermal protection switches load to bypass in case of overheating.
Storage Temperature -20°C to 40°C (-4°F to 104°F) with batteries
-25°C to 55°C (-13°F to 131°F) without batteries
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–90% noncondensing
Operating Altitude Up to 3,000 meters (9,843 ft) above sea level
Transit Altitude Up to 10,000 meters (32,808 ft) above sea level
Audible Noise <50 dBA at 1 meter typical
Leakage Current <1.5 mA
Table 9 Battery Runtimes (in Minutes) at 100% Load
Model Internal Batteries +1ERM +2ERMs +3ERMs +4ERMs
HP R3000v UPS 3 18 34 53 69
Table 10 Battery
Internal Batteries Extended Runtime Modules
Configuration 72 Vdc (6 12V, 9 Ah) HP R3000v ERM: 72 Vdc (2x6 12V, 9 Ah)
Fuses Not applicable (4) 30A/125 Vdc fuses per ERM
Type Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life at 25°C (77°F)
Monitoring Advanced monitoring for earlier failure detection and warning
Recharge Time 3 hours to 90%
Battery Port External three-pole Anderson connector on UPS for connection to ERM