HP Value UPS Manager User Manual
23
Diagram 3-2-7-1
Note: "High limit of input frequency on bypass", "Low limit of input frequency on bypass", "High limit of
input voltage on bypass" and "Low limit of input voltage on bypass" can only be set successfully when the
UPS is in standby mode.
See the following table 3-2-7-1:
Parameter Unit Maximum Minimum Default
High limit of input frequency on bypass
% 10 2 10
Low limit of input frequency on bypass % 10 2 10
High limit of input voltage on bypass % 20 4 10
Low limit of input voltage on bypass % 20 4 15
ERM number - 4 0 -
ON button can control battery mode
audible warning
- - - Yes
ON button can control bypass mode
audible warning
- - - Yes
Do audible warning when on bypass
mode
- - - Yes
Do audible warning when on battery
mode
- - - Yes
Restore line mode when AC restored - - - Yes