UPS R12000 XR Models Maintenance and Service Guide

Table Of Contents
Safety and Product Information
1-4 HP UPS R12000 XR Models Maintenance and Service Guide
Remote Emergency Power Off
The UPS includes a Remote Emergency Power Off (REPO) port. When properly wired, the
REPO port allows the power at the UPS output receptacles to be switched off from a remote
location. Local or national wiring regulations may require REPO capabilities.
WARNING: To prevent personal injury or damage to equipment, take the following
precautions:
The REPO port must be wired by a qualified electrician.
The main breaker switch must be in the off position before wiring the REPO port.
Remote circuits connected to the REPO port must comply with local building
wiring codes and methods. In North America, the NEC (NFPA 70, Article 725) is a
minimum requirement.