HP Virtual Connect for c-Class BladeSystem Setup and Installation Guide
Installation  27 
IMPORTANT: In a single enclosure domain, HP recommends that you do not manage the VC 
domain from HP 1/10 Gb VC-Enet Modules or HP 1/10 Gb-F Ethernet Modules if FlexFabric 
modules exist in the same enclosure. 
In a multi-enclosure domain, you cannot manage the VC domain from HP 1/10 Gb VC-Enet 
Modules or HP 1/10 Gb-F Ethernet Modules if HP VC Flex-10 and FlexFabric modules are present 
in the same enclosure. However, homogeneous 1/10 Gb module multi-enclosure configurations 
are acceptable. 
The VC-FC modules and FlexFabric FC-configured ports do not support stacking. Connecting multiple 
enclosures requires identical FC and FlexFabric module bay configuration in each enclosure. For more 
information, see "FC and FlexFabric bay configuration using multiple enclosures (on page 27)." 
Multi-enclosure double dense domains require similar and compatible FC modules in bays 5, 6, 7, and 8 in 
all enclosures. If a multi-enclosure double dense configuration contains incompatible FC modules in bays 5, 
6, 7, or 8 in either the local or remote enclosures, some or all of the compatible FC modules in the remote 
enclosures might be designated INCOMPATIBLE after import. 
To add additional enclosures to a domain, see the HP Virtual Connect for c-Class BladeSystem User Guide 
on the Installing tab of the HP BladeSystem Technical Resources website 
(http://www.hp.com/go/bladesystem/documentation). 
FC and FlexFabric bay configuration using multiple enclosures 
The VC-FC modules and FlexFabric FC-configured uplinks do not support stacking. To ensure server profile 
mobility, the VC-FC and FlexFabric bay configurations must be identical for all enclosures in the domain. 