HP StorageWorks Disk Array XP1024: Site Preparation Guide (A7906-96013, July 2005)

Preparing for installation 33
The figure below shows the maximum service access and cutouts for the
XP1024.
Clearance (a+b) depends on the floor load rating and clearance (c). The
following table lists floor load ratings.
If your installation will include one or more XP512 DKUs, see the HP
StorageWorks Disk Array XP512 Site Preparation Guide for XP512
clearance requirements.
Floor Load Rating
(kg/m
2
)
Clearance (C) (m)
C = 0 C = 0.2 C = 0.4 C = 0.6 C = 1.0
500 1.9 1.2 0.8 0.3 0
450 2.7 2.0 1.4 1.0 0.7
400 3.9 3.1 2.4 1.8 1.0
350 5.6 4.6 3.7 3.1 2.0
300 8.3 6.9 3.9 5.0 3.7
Floor cutout area for cables
Caster
Screw jack
Service clearance
3782
Front
G
Grid panel (over 450mm x 450mm)
a *1
DKU
16
C *1
(Unit: mm)
800
2400
800
800
b *1
G
16
G
750
G
750
G
750
G
750
G
750
G G G G
DKU DKC DKU DKU