HP StorageWorks Disk Array XP1024: Site Preparation Guide (A7906-96013, July 2005)

40 HP StorageWorks Disk Array XP1024: Site Preparation Guide
The table below lists the basic AC power requirements for a 30-amp,
three-phase XP1024 DKC.
Parameter
Nominal Rated Voltage (VAC)
200 208* 220 230 240 380 400 415
Minimum operating
voltage (VAC)
184 191 202 212 221 350 368 382
Maximum operating
voltage (VAC)
212 220 233 244 254 403 424 440
Rated line current
per power cord (amps
RMS)
5.2 5.0 4.7 4.6 4.3 2.7 2.6 2.5
Number of power
cords
22222222
Recommended circuit
breakers (amps)
30 30 30 30 30 30 30 30
Number of circuit
breakers
22222222
Dropout
carry-through time at
minimum line voltage
(ms)
30 30 30 30 30 30 30 30
* 60 Hz only.