HP StorageWorks Disk Array XP1024: Site Preparation Guide (A7906-96013, July 2005)
44 HP StorageWorks Disk Array XP1024: Site Preparation Guide
The table below lists the basic AC power requirements for 60-amp,
three-phase, R2, L1, and L2 XP1024 DKUs. Unlike the first DKU (R1),
DKUs R2, L1, and L2 do not provide AC power to the DKC.
Parameter
Nominal Rated Voltage (VAC)
200 208
1
220 230 240 380 400 415
Minimum operating
voltage (VAC)
184 191 202 212 221 350 368 382
Maximum operating
voltage (VAC)
212 220 233 244 254 403 424 440
Rated line current per
power cord
(amps RMS)
19.0 18.2 17.2 16.6 15.7 10.7 10.2 9.8
Number of power
cords
2 2 2 2 2 2 2 2
Recommended
circuit breakers
(amps)
60 60 60 60 60 30
min.
2
30
min.
2
30
min.
2
Number of circuit
breakers
2 2 2 2 2 2 2 2
Dropout
carry-through time at
minimum line voltage
(ms)
30 30 30 30 30 30 30 30
1. 60 Hz only.
2. 30-amp breakers are adequate at 380, 400, and 415 VAC, because the
current drawn at these voltages is considerably less than at the lower
voltages.