HP StorageWorks Disk Array XP1024: Site Preparation Guide (A7906-96013, July 2005)
68 HP StorageWorks Disk Array XP1024: Site Preparation Guide
Power requirements: single secondary input (primary offline)
The values in the table below are based on a worst-case voltage (rated
voltage –10%) and a maximum configuration for disk control and disk
array frames. A phase imbalance of 15% is also included in the calculation.
In a maximum XP1024 configuration (1 DKC and 4 XP1024 DKUs) the
array requires 31 kVA.
If you intend to use HP Disk Array XP512 DKUs with your
HP Disk Array XP1024, see the HP StorageWorks Disk Array XP512 Site
Preparation Guide for power requirements for these DKUs.
Reference supplier information
American Power Conversion
32 Fairgrounds Road
West Kingston, RI 0289
Phone Numbers:
Technical Support & Product Info.
1-800-800-4272
Corporate
1-800-788-2208
1-401-789-5735
To find out more about the recommended American Power Conversion
UPS, travel to the APC web site:
www.apcc.com
You can also contact your HP service representatives for specific
configuration needs for your area.
Input (VAC) Single-Phase Three-Phase
208 DKC Each
DKU
First DKU Each Additional
DKU
13.1 A 36.8 A 31 A 24.6 A
400 N/A N/A 17.4 A 14.4 A