HP StorageWorks Disk Array XP1024: Site Preparation Guide (A7906-96013, July 2005)
Preparing for installation 73
Heat dissipation and power consumption
The table below describes the heat dissipation and power consumption of
the HP Disk Array XP1024 in a maximum configuration:
If you intend to use HP Disk Array XP512 DKUs with your HP XP1024
Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation
Guide for heat dissipation and power consumption information for these
DKUs.
Parameter DKC Each DKU
Full Array
(4 DKUs &
1 DKC)
Power consumption (kVA) 3.09 6.94 30.85
Heat dissipation (kW) 2.94 6.40 28.53
BTUs per hour 10034 21843 97373
kcal per hour 2528 5504 24536