HP StorageWorks Disk Arrays XP128/XP1024 Owner's Guide (A7906-96012, July 2005)
42 HP StorageWorks Disk Arrays XP128/XP1024 Owner’s Guide
Mechanical vibration
AC line voltage
The following AC power recommendations for the HP StorageWorks Disk
Array XP128 are for each power cord. Each array frame has two power
cords (with the AC power cord option there are four cords). In case of a
failure of the power source for one cord, the power requirements and the
current requirement for the remaining power cord will double.
Table 7 (page 42) lists the basic AC power requirements for a 50-amp
single-phase XP128 DKU. Table 8 (page 43) lists the basic AC power
requirements for a 30-amp single-phase XP128 DKU.
Table 6. Mechanical vibration
Mechanical vibration
Maximum Operating
Acceleration
0.05G at a frequency range of 10 to 300 Hz
Table 7. 50-Amp, 50 or 60 Hz, Single-Phase DKU Operation
Parameter
Nominal Rated Voltage (VAC)
200 208* 220 230 240
Rated line current per
power cord (Arms)
16.2 15.1 14.9 14.3 13.8
Number of power cords22222
Number of circuit
breakers
22222
Recommended circuit
breakers
50A 50A 50A 50A 50A
* 60 Hz only.