HP XP7 Getting Started Guide

Table 7 Data communication requirements (continued)
Column HeadColumn Head
representative will configure C-Track, contact your HP
representative.
Needed to connect the HP system to an available Ethernet
port on the customer's LAN. To ensure network security,
A twisted pair (Cat 5) cable.
consult with an HP representative and your network
administrator before selecting the appropriate location of
your LAN drop.
Needed to allow your staff and HP representatives to
communicate inside and outside your site.
A public voice phone line near the disk array.
C-Track
The C-Track remote support solution detects and reports events to the HP Support Service. C-Track
transmits heartbeats, SIMs, and configuration information for remote data collection and monitoring
purposes. C-Track also enables the HP Support Service to remotely diagnose issues and perform
maintenance (if the customer allows the remote maintenance). The C-Track solution offers Internet
connectivity only. If you choose the Internet-based remote support solution, additional infrastructure
and site preparation are required. Additional preparation may include server and router
requirements, which you and HP may be responsible for implementing.
System specifications and requirements
Service clearance, floor cutout, and floor load rating
This section describes the service clearance requirements for the HP XP7 disk array, based on the
floor load rating and the clearance and required floor cutouts for cabling. The figures and tables
that provide this information are listed in the following table.
Table 8 Service clearance and floor load ratings
Service Clearance and Floor Load Rating
SectionNumber of racks
“Single rack configuration” (page 23)1
“Two rack configuration (one DKC)” (page 24)2
“Two rack configuration (two DKC)” (page 26)2 (two DKC)
“Three rack configuration (left module)” (page 27)3 (left module)
“Three rack configuration (right module)” (page 29)3 (right module)
“Four rack configuration (left module)” (page 30)4 (left module)
“Four rack configuration (right module)” (page 32)4 (right module)
“Five rack configuration” (page 33)5
“Six rack configuration” (page 35)6