Figure 8 Service clearances for a two rack system (single DKC)
*1 Clearance (a+b) is based on the floor load rating and the clearance (c). Floor load rating and
required clearances are shown in Table 10 (page 25).
*2 Clearance (d) is required over 300mm to open the front door. In the case that the clearance
(d) is less tan the clearance (a), give priority to clearance (a).
Table 10 Floor load rating and required clearances for two rack configuration
Required Clearance (a+b) mFloor Load
Clearance (c) mRating
(kg/m2)
C=1.4C=1.0C=0.8C=0.6C=0.4C=0.2C=0C=-0.3
00000000Over 700
00000000.1600
000000.10.20.4500
0000.10.20.30.40.6450
00.20.30.40.50.60.71.0400
0.30.50.60.70.81.01.21.5350