Installation Instructions

Consider installing the following additional components:
Ball valvesInstall ball valves between the connection of the
water hoses and the facility water supply to enable you to
easily turn off the facility water to the MCS G2 unit for any
reason. If you do not install ball valves, water will drain from
the facility piping when you disconnect the hose.
Filter and bypassInstall a filter to aid in the quality of water
entering the MCS G2 unit. Install a bypass for the filter to aid in
the operation and cooling of your equipment.
Pressure reducing valveInstall a pressure reducing valve if the
pressure of your MCS G2 unit is over the maximum operating
pressure of the MCS G2 , approximately 100 psi (6.9 bar).
For more recommendations and installation examples, see the HP
Modular Cooling System G2 Site Preparation User Guide on the HP
website (http://www.hp.com/go/rackandpower
).
Orientation of the hose
The hoses have swivel nuts on both ends, making it difficult to
differentiate which end connects to the MCS G2 and which end
connects to your facility water. Mechanically, you can connect either
end to either location.
For easy installation, connect the end with the clam shell to your
facility.
Removing the cap from the T-fitting
on the MCS G2 unit
Determine if you are going to install the main hoses up through a
hole in your raised floor or if the hoses will lie on top of your floor.
If you are going to route your hoses through a hole in a raised
floor, use the cap wrench to remove the cap from the bottom
legs of the T-fittings, and be sure the caps are secure on the
side of the T-fittings.
If you are going to lay your hoses across the top of the floor,
use the cap wrench to remove the cap from the side arms of the
T-fittings, and be sure the caps are secure on the bottom of the
T-fittings.
Attaching the main hoses to the
MCS G2 unit
1. Attach the main hoses to the appropriate side of the T-fitting on
the MCS G2 unit, and hand tighten.
Callout Component Function
A
Main water hose-
Inlet
Brings cold water in to the MCS
G2 unit
B
Main water hose-
Outlet
Removes hot water from the
MCS G2 unit