MPE/iX System Utilities Reference Manual (32650-90908)

UPSUTIL for MPE/iX
UPSUTIL Commands
Chapter 32
256
--------------------------------------------------------------------------
UPSUTIL: Command > status
--------------------------------------------------------------------------
Begin display of UPS Monitor status.
UPS MONITOR PROCESS STATUS:
UPS Monitor Operating State : Running (PIN = 196)
UPS Monitor Version Number : 9 3 UPS Devices Configured
System Power State : Power has failed. 3 UPS Devices Monitored
Powerfail Recovery Messages : All terminals. 3 UPS Devices Allocated
Configuration File Name : UPSCNFIG.PUB.SYS ( Config File Ok )
Powerfail Command File Name : MYPFAIL.PUB.MYACCT ( Pfail Cmd File Ok )
Powerfail Command File Parms: [inventory_data_set orders_data_set]
Powerfail Grace Period (secs: 300
Powerfail Grace Timer : Running.
Powerfail Command File : Not Running.
Action on UPS Low Battery : Keep Running
UPS DEVICES STATUS:
UPS# Ldev# Alloc Init State Power Hardware Status
~~~~ ~~~~~~ ~~~~~ ~~~~ ~~~~~~~~~~~~ ~~~~~~ ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
1 22 Yes Yes Monitoring Normal AC Power Normal
2 23 Yes Yes Monitoring Failed AC Power Fail
3 24 Yes Yes Monitoring Normal AC Power Normal
End display of UPS Monitor status.
--------------------------------------------------------------------------
UPSUTIL: Command >
Example #4 AC Power Failure Timed-Out
This example shows a status display following an incoming AC power failure condition at one of the UPS
devices and after the configured Powerfail Grace Period Timer has expired. This has caused the users
Powerfail Command File to begin execution.
In this case, you can see in the UPS MONITOR PROCESS STATUS that the System Power State is Power
has failed, the configured Powerfail Grace Period timer has expired, and the Powerfail Command File is
now in execution. (Running).
The UPS DEVICES STATUS portion of the display shows that UPS LDEV #23 has reported an AC Power
Fail hardware status condition, and so its Power condition field has been changed to Failed.