Getting Started Guide

Site requirements 12
Front view shown
Utilities
Consider the proximity to required utilities, such as power, water, and network connections. While the
required utilities can be brought to nearly any selected site, there is the potential for increased costs and
decreased efficiency when the HP POD 20c is located farther from the utility sources.
For utility clearance information, see "Dimensions and clearances (on page 8)."
Humidifier water supply
The HP POD 20c requires supply water for the humidifier. The supply water must meet the following
requirements.
Requirement Specification
Pressure
Between 20 and 110 psi, 0.1 and 0.8 MPa
Temperature
Between 1º and 40°C (33º and 104°F)
Minimum flow rate
1.45 lpm (0.12 gpm)
Connection
1.9 cm (.75 in) G
Adapter to 1.9 cm (.75 in) FPS
Hardness
No greater than 40°fH (equal to 400 ppm of CaCO
3
)
Conductivity
100 to 1250 μS/cm
Organic compounds
None
Type of water
Drinking water. Do not use de-mineralized or softened water.
Instant water fill flow
rate
0.6 lpm (0.16 gpm)
Humidifier
For the exact requirements, see the humidifier documentation.
IMPORTANT: If your water is out of range, consult a water quality expert.
In addition to the previous requirements, observe the following requirements and recommendations: