Service and Maintain

Removal and replacement procedures 16
The HP standard suppression system includes a Novec 1230 clean agent system. However, if the customer
or local AHJ requires specific modifications or a replacement, HP can assist in these actions at the expense
of the customer.
HP does not certify that the fire suppression system installed in the HP POD 40c G2 meets all local and
jurisdictional requirements. The customer is responsible for the following actions as related to the fire
suppression system:
Verifying that the POD suppression system meets local codes, including specific local requirements for
initial and periodic inspections.
Arranging for and receiving all required local permits, including initial commissioning as well as
standard and repair maintenance.
Arranging for the connection of the agent tanks, refilling of tanks, and all system testing, including
pressure tests. All general maintenance of the suppression system must be completed by an authorized
technician.
Additional local requirements are not covered as part of the option price or basic installation and
deployment services, unless specifically included in an executed Statement of Work.
Air filter
There are 2 air filters per cooling zone, for a total of 12 filters.
Tools are not required for installation.
Removing the air filter
1. Pull the locking tabs away from the air filter to release the filter.