ProLiant ML110 Gen10 Server

QuickSpecs
HPE ProLiant ML110 Gen10 Server
Technical Specifications
Page 35
System Unit
Tower Dimensions
17.32 (H)x 7.68.(W) x 18.92. (D) in (44 x 19.5 x 48.05 cm)
Tower Weight
(approximate)
Minimum:
29.82 lbs (13.5 kg)
Maximum:
55.0 lbs (25.0 kg)
Input Requirements
(per power supply)
Rated Line Voltage
100 to 120 VAC
Rated Input
Frequency
For 350W & 550W Power Supply:8A (at 100~240 VAC)
50 to 60 Hz
Rated Input
Power
For 550 W Power Supply:< 639 W (at 100 VAC),< 605 W (at 200 VAC)
For 350 W Power Supply:< 427 W (at 100 VAC),< 427 W (at 200 VAC)
BTU Rating
Maximum
For 550 W Power Supply:2204 BTU/hr (at 100 VAC),2113 BTU/hr (at
200 VAC)
For 350 W Power Supply:1452 BTU/hr (at 100 VAC),1544 BTU/hr (at
200 VAC)
Power Supply Output
(per power supply)
Rated Steady-State Power
For 550 W Power Supply:550 W (at 100 VAC),550 W (at 200 VAC),
Maximum Peak Power
For 350 W Power Supply:350 W (at 100 VAC),350 W (at 200VAC),
System Inlet Temperature
Standard Operating
Temperature
10° to 35°C (50° to 95°F) at sea level with an altitude derating of 1.0°C
per every 305 m (1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct sustained sunlight
.
Maximum rate of change is 20°C/hr (36°F/hr)
. The upper limit and rate
of change may
be limited by the type and number of options installed.
System performance during standard operating support may be
reduced if operating with a fan fault or above 30°C (86°F).
Extended Ambient
Operating Support
For approved hardware configurations, the supported system
inlet range is extended to be: 5° to 10°C (41° to 50°F) and
35° to 40°C (95° to 104°F) at sea level with an altitude
derating of 1.0°C per every 175 m (1.8°F per every 574 ft)
above 900 m (2953 ft) to a maximum of 3048m (10,000 ft).
The a
pproved hardware configurations for this system are
listed at the URL:
http://www.hpe.com/servers/ashrae.
System performance may be reduced if operating in the extended
ambient operating range or with a fan fault.
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of change is 20°C/hr
(36°F/hr).
Relative Humidity
Operating
8% to 90% - Relative humidity (Rh), 28°C maximum wet bulb
temperature, non-condensing.
(non-condensing)
Non-operating
5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb
temperature, non-condensing..
Altitude
Operating
3050 m (10,000 ft). This value may be limited by the type and number
of options installed. Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft). Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Acoustic Noise
Listed are the declared A-Weighted sound power levels (L
WAd
) and declared average bystander
position A
-Weighted sound pressure levels (L
pAm
) when the product is operating in a 23°C ambient
environment. Noise emissions were measured in accordance with ISO
7779 (ECMA 74) and
declared in accordance with ISO 9296 (ECMA 109). The listed sound levels apply to standard
shipping configurations. Additional options may result in increased sound levels. Please have your
HPE representative provide information from th
e HPE EMESC website for further technical details
regarding the configurations listed below.