User Manual
Table Of Contents
- HPE ProLiant MicroServer Gen10 Plus User Guide
- Contents
- Component identification
- Operations
- Setup
- Hardware options installation
- Cabling
- Software and configuration utilities
- Server mode
- Product QuickSpecs
- Active Health System Viewer
- HPE iLO 5
- Integrated Management Log
- Intelligent Provisioning
- Management security
- Scripting Toolkit for Windows and Linux
- UEFI System Utilities
- HPE Smart Storage Administrator
- HPE InfoSight for servers
- USB support
- Redundant ROM support
- Keeping the system current
- Troubleshooting
- System battery replacement
- Safety, warranty, and regulatory information
- Specifications
- Websites
- Support and other resources
System battery replacement
System battery information
The server contains an internal lithium manganese dioxide, a vanadium pentoxide, or an alkaline battery that provides
power to the real-time clock. If this battery is not properly handled, a risk of the fire and burns exists. To reduce the risk of
personal injury:
• Do not attempt to recharge the battery.
• Do not expose the battery to temperatures higher than 60°C (140°F).
• Do not expose the battery to extremely low air pressure as it might lead to explosion or leakage of flammable liquid or
gas.
• Do not disassemble, crush, puncture, short external contacts, or dispose the battery in fire or water.
• If the server no longer automatically displays the correct date and time, then replace the battery that provides power
to the real-time clock. Under normal use, battery life is 5 to 10 years.
Removing and replacing the system battery
Prerequisites
Before you perform this procedure, make sure that you have a small flat-bladed, nonconductive tool available.
Procedure
1.
Power down the server.
2.
Disconnect the power cord from the AC source.
3.
Remove the power adapter cord from the power cord clip, and then disconnect the power adapter from the server.
4.
Disconnect all peripheral cables from the server.
5.
If the server is in a vertical orientation, position the server in a horizontal orientation.
System battery replacement
79