above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft). The
approved hardware configurations for this system are listed at the
URL:
http://www.hpe.com/servers/ashrae
System performance may be reduced if operating in the extended
ambient operating range or with a fan fault.
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of change is 20°C/hr
(36°F/hr).
Relative Humidity
Operating
8% to 90% - Relative humidity (Rh), 28°C maximum wet bulb
temperature, non-condensing.
(non-condensing)
Non-operating
5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb
temperature, non-condensing..
Altitude
Operating
3050 m (10,000 ft). This value may be limited by the type and number
of options installed. Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft). Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Acoustic Noise
Listed are the declared A-Weighted sound power levels (L
WAd
) and declared average bystander
position A
-Weighted sound pressure levels (L
pAm
) when the product is operating in a 23°C ambient
environment. Noise emissions were measured in accordance with
ISO 7779 (ECMA 74) and
declared in accordance with ISO 9296 (ECMA 109). The listed sound levels apply to standard
shipping configurations. Additional options may result in increased sound levels. Please have your
HPE representative provide information fr
om the HPE EMESC website for further technical details
regarding the configurations listed below.
Idle
LWAd
4.8 B Entry
4.4 B Base
4.6 B Perf
LpAm
37 dBA Entry
31 dBA Base
31 dBA Perf
Operating
LWAd
4.8 B Entry
4.4 B Base
4.6 B Perf
LpAm
37 dBA Entry
31 dBA Base
31 dBA Perf
NOTE: Acoustics levels presented here are generated by the test configuration only. Acoustics
levels will vary depending on system configuration. Values are subject to change without
notification and are for reference only.
NOTE: Product conformance to cited product specifications is based on sample (type) testing,
evaluation, or assessment. This product or family of products is eligible to bear the appropriate
compliance logos and statements.
NOTE:
The Listed sound levels apply to standard shipping configurations. Additional options
may result in increased sound levels.
Emissions Classification
(EMC) Regulatory
Information
To view the regulatory information for your product, view the Safety and Compliance Information
for Serve
r, Storage, Power, Networking, and Rack Products, available at the Hewlett Packard
Enterprise Support Center:
http://www.hpe.com/support/Safety-Compliance-EnterpriseProducts