User Manual
Table Of Contents
- HPE ProLiant DL160 Gen10 Server User Guide
- Contents
- Important product information
- Component identification
- Setup
- Operations
- Power up the server
- Powering down the server
- Extend the server from the rack
- Access the product rear panel
- Remove the server from the rack
- Removing the front bezel
- Remove the access panel
- Installing the access panel
- Removing the primary PCI riser blank
- Installing the primary PCI riser blank
- Removing the primary PCI riser cage
- Installing the primary PCI riser cage
- Removing the secondary PCI riser cage
- Installing the secondary PCI riser cage
- Removing the expansion slot blank
- Removing and replacing a drive blank
- Hardware options installation
- Introduction
- Installing the front bezel option
- Redundant power supply enablement option
- Power supply options
- Memory options
- Drive options
- Installing a two-bay SFF enablement kit
- Installing the Slim SSD enablement kit
- Redundant fan option
- Installing the optical drive
- Installing the Media Module
- Installing the FlexibleLOM
- Installing the serial port
- Expansion board options
- Storage controller options
- Processor heatsink assembly option
- Installing the Chassis Intrusion Detection switch
- Smart Storage Battery option
- M.2 SSD enablement option
- HPE Trusted Platform Module 2.0 Gen10 option
- Cabling
- Software and configuration utilities
- Troubleshooting
- System battery replacement
- Specifications
- Safety, warranty, and regulatory information
- Websites
- Support and other resources
https://myenterpriselicense.hpe.com
Operational requirements
Space and airflow requirements
To allow for servicing and adequate airflow, observe the following space and airflow requirements when
deciding where to install a rack:
• Leave a minimum clearance of 63.5 cm (25 in) in front of the rack.
• Leave a minimum clearance of 76.2 cm (30 in) behind the rack.
• Leave a minimum clearance of 121.9 cm (48 in) from the back of the rack to the back of another rack
or row of racks.
Hewlett Packard Enterprise servers draw in cool air through the front door and expel warm air through the
rear door. Therefore, the front and rear rack doors must be adequately ventilated to allow ambient room
air to enter the cabinet, and the rear door must be adequately ventilated to allow the warm air to escape
from the cabinet.
CAUTION: To prevent improper cooling and damage to the equipment, do not block the ventilation
openings.
When vertical space in the rack is not filled by a server or rack component, the gaps between the
components cause changes in airflow through the rack and across the servers. Cover all gaps with
blanking panels to maintain proper airflow.
CAUTION: Always use blanking panels to fill empty vertical spaces in the rack. This arrangement
ensures proper airflow. Using a rack without blanking panels results in improper cooling that can
lead to thermal damage.
The 9000 and 10000 Series Racks provide proper server cooling from flow-through perforations in the
front and rear doors that provide 64 percent open area for ventilation.
CAUTION: When using a Compaq branded 7000 series rack, install the high airflow rack door insert
(PN 327281-B21 for 42U rack, PN 157847-B21 for 22U rack) to provide proper front-to-back airflow
and cooling.
CAUTION: If a third-party rack is used, observe the following additional requirements to ensure
adequate airflow and to prevent damage to the equipment:
• Front and rear doors—If the 42U rack includes closing front and rear doors, you must allow
5,350 sq cm (830 sq in) of holes evenly distributed from top to bottom to permit adequate airflow
(equivalent to the required 64 percent open area for ventilation).
• Side—The clearance between the installed rack component and the side panels of the rack must
be a minimum of 7 cm (2.75 in).
Temperature requirements
To ensure continued safe and reliable equipment operation, install or position the system in a well-
ventilated, climate-controlled environment.