Datasheet
H S B H S B
Industrieelektronik Industrieelektronik
|H|S|B| Industrieelektronik GmbH Hans-Boerdlein-Str. 10 97723 Oberthulba |H|S|B| Industrieelektronik GmbH Hans-Boerdlein-Str. 10 97723 Oberthulba
Tel: 09736/75759-0 Fax: 09736/75759-20 E-mail: info@hsb-electronics.de Internet: www.hsb-electronics.de Tel: 09736/75759-0 Fax: 09736/75759-20 E-mail: info@hsb-electronics.de Internet: www.hsb-electronics.de
Mounting
Snap-on mounting using a standard DIN rail EN 50022.
The unit is designed to allow side-by-side mounting, with an ambient temperature of < 60°C.
manual
Multifunctions timer ZMR
microcontrollerswitched
serie 17,5 mm
article – nr. ZMR1 – 11.021.00.001
ZMR2 – 11.022.00.001
Technical data
Supply voltage A1 / A2: 230V AC +/- 15%
A3 / A2: 24V AC/DC +/- 15%
Frequency range: 0 / 50 ... 60Hz
Power consumption: approx. 1.0 W with 24V AC/DC
approx. 6 VA with 230V AC
Operating mode: continuous
Supply voltage influence: < 0.01% over voltage range
Temperature influence: < 0.01%/°C
Recovery time: > 100ms
Repetitive accuracy: 0.2%
Timing range : 0,05s - 10h (8 time ranges)
Operation indicators
Supply voltage: LED, green
Relay in working position: LED, yellow
Contact
Number of changeovers: 1 or 2
Contact material: AgNi 0,15
Maximum switching voltage: 400V AC
Maximum switching current: 8A
Maximum switching power : 2000VA
contact live : 30 x 10
6
(mechanical)
Drop-off time of switching element: approx. 20ms
General data
Ambient temperature: - 25 ... + 60°C
Mounting position: any
LVD 2006/95/EG : 61812-1
EMC Dir. 2004/108/EG : 61812-1
overvoltage category : 3 (300V)
contamination degree : 2 (250V)
test voltage : 4kV (1,2/50µs)
Isolation : 15/16/18 -> A1/A2/A3/B1/B2 >3mm ; basic isolation (250V)
25/26/28 -> A1/A2/A3/B1/B2 >3mm ; basic isolation (250V)
15/16/18 -> 25/26/28 >6mm ; double isolation (250V)
Connection terminals: Crosshead screws; M3.5 self-opening
Connection cross section: 2 x 2.5mm²
Mounting: Symmetrical rail DIN EN 50022
Dimensions l x w x h: 90mm x 17.5mm x 69.5mm
Weight: ZMR1 - 96g ZMR2 - 104g
X
X
X
X
B2
15A2
16 18
B1
A3A1
X
28
25 26
B2
15A2
16 18
B1
A3A1
ZMR1 ZMR2
A2
B2
K1
15
18
A1
B1
K1
A1
A2
A3
B1
B2
15
16 18
15
16 18
25
26 28
6
5
4
3
2
Time
Function
33 3 3 33
22 2 2 22
Ansprechverzögert ; On delay ; Retard á la mise sous tension
Abfallverzögert ; Off delay ; Retard au déclenchement*
Einschaltwischend ; Single pulse on ; Temporisation á la mise sous tension
Blinkend-Pause ; Flasher beginning with off ; Clignotant démarrant par une impulsion
Blinkend-Impuls ; Slasher beginning with on ; Clignotant démarrant par une coupure
6
5
6
5
6
5
6
5
6
5
6
5
4 44 4 44
0,05 - 1s
0,5 - 10s
3 - 60s
15 - 300s
0,5 - 10 min.
3 - 60 min.
15 - 300 min.
0,5 - 10 h
3
2
1
3
2
1
Watchdog*
6
5
4
* these functions are required for B1and B2
6
5
4